Description

Lynx series, with output power factor 0.9,  can easily adapt to all kinds of diverse and complicated loads, such as the non-linear systems (IT systems), strongly inductive or capacitive loads, discharge lamps, and induction motors. To meet diverse applications, it is allowed to have alternative battery configuration based on different backup time requirement. To facilitate expansion easily, this unit can be set up in parallel-redundant systems with up 4 units.

Specifications

      • Online double conversion technology with DSP (Digital Signal Processor) control
      • DSP technology guarantees high performance
      • Output power factor 0.9
      • Advanced control with Adaptive Feed Forward Cancellation (AFC) technology for very low harmonic distortion
      • Very low input current distortion (THDi < 1%)
      • Input power factor 0.99 at 10% load
      • Output efficiency up to 95%
      • Space saving compact design
      • Over 60% materials recyclable
      • Front access for easy maintenence
      • High flexibility in single phase/ three phase set-ups
      • Parallel redundant operation with up to 4 units
      • Variety of communications options available
      • Flexible battery type configuration
      • NEXTVision shutdown software suite
      • 5.7" graphic LCD panel design with multiple languates for easy-configuration
      • 2 years NEXT Onsite warranty
    • MODEL

      Lynx
      10 kVA

      Lynx
      15 kVA

      Lynx
      20 kVA

      Lynx
      30 kVA

      Lynx
      40 kVA

      Lynx
      60 kVA

      PHASE

      3-phase in / 3-phase out

      CAPACITY

      10000VA/
      9000W

      15000VA/
      13500W

      20000VA/
      18000W

      30000VA/
      27000W
      40000VA/
      36000W
      60000VA/
      54000W

      INPUT

      Nominal Voltage

      3 x 400V (3Ph+N)

      Acceptable Voltage Range

      +15% or -20%

      Frequency

      50/60 Hz +/-5%

      Total Harmonic Distrotion (THDi)

      < 1.5% @ 100% load
      < 2.5% @ 50% load
      < 6.0% @ 10% load

      < 1.0% @ 100% load
      < 2.0% @ 50% load
      < 5.0% @ 10% load

      Current Limitation

      High overload: PFC Limit (discharging batteries)

      Power Factor

      1.0

      INVERTER

      Nominal Voltage

      3 x 400V (3Ph + N)

      Precision

      Stationary: ±1%    
      Transitory: ±2% (load variations 100-0-100%)

      Frequency

      50/60 Hz synchronised ±4 %
      With mains absent ±0.05%

      Max. Synchronisation Speed

      ±10 Hz/s

      Waveform

      Pure Sinewave

      Total Harmonic Distortion (THDv)

      <0.5% (Linear Load)
      <1.5% (Non-linear Load)

      Phase Displacement

      120º ±1% (balanced load)
      120º ±2% (imbalances 50% of the load)

      Dynamic Recovery Time

       10 ms. at 98 % of the static value

      Admissible Overload

      Phase Overload:125% for 10 min., 150% for 60 s  Total Over load:112.5% for 10 min., 135% for 60 s

      Admissible Crest Factor

      3.4 : 1

      3.2 :1

      Admissible Power Factor

      0.7 inductive to 0.7 capacitive 

      Imbalance Output Voltage @ 100% Unbalanced Load 

      <1% 

      Current Limit

      High overload, short-circuit: RMS Voltage Limit
       High Crest-Factor current: Peak Voltage Limit 

      Type

      Solid state 

      Voltage

       3x400V (3Ph + N)

      Frequency

      50/60 Hz 

      Activation Criterion

      Microprocessor control 

      Transfer Time 

       Zero seconds

      Admissible Overload

       400% for 10 sec.

      Transfer to Bypass

      Immediate, for overloads above 150%

      Retransfer

      Automatic after alarm clear

      Type

      Without interruption

      Voltage

      3 x 400V (3Ph + N)

      Frequency 

      50/60 Hz 

      Overall Efficiency (Line mode)

       90,00%

      90,50%

      91,00%

      92,00%

      92,50%

      93,00%

      Dimensions, D x W x H(mm)

      700 x 450 x 1100 

      Net Weight (without batteries) (Kg)

      120

      160

      190

      Built-in Battery Type (2x31)

       12V 9Ah

      12V 12Ah

      -

      Back-up Time (minutes)

      23 

      10,6

      7,8

      3,8

      3,5

      -

      Net Weight (w/built-in batteries) (Kg)

      292

      292 292 332 420 -

      MANAGEMENT

      Smart RS-232 / USB

      Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7, Linux, Unix, and MAC

      Optional SNMP

      Power management from SNMP manager and web browser

      NEXT PARTNUMBERS

      LYNX UPS

      77130 

      77131

      77132

      77133 77134 77135

      LYNX Battery extension

      77136

      77136

      77136 

      77136 77137 BTO

      SNMP/WEB Interface

      included

      included

      included

      included included included
      * Product specifications are subject to change without further notice.

    • MODELLynx 
      80 kVA
      Lynx 
      100 kVA
      Lynx 
      120 kVA
      Lynx 
      1600 kVA
      Lynx 
      200 kVA
      PHASE 3-phase in / 3-phase out
      CAPACITY 80000VA/
      72000W
      10000VA/
      90000W
      120000VA/
      108000W
      160000VA/
      144000W
      200000VA/
      180000W
      INPUT
      Nominal Voltage 3 x 400V (3Ph+N)
      Acceptable Voltage Range +15% or -20%
      Frequency 50/60 Hz +/-5%
      Total Harmonic Distrotion (THDi)

      <1.0%@100% load
      <2.0%@50% load
      <5.0%@10% load
      < 1.5% @ 100% load
      < 2.0% @ 50% load
      < 6.0% @ 10% load

      Current Limitation

      High overload: PFC Limit (discharging batteries)

      Power Factor

      1.0

      INVERTER

      Nominal Voltage

      3 x 400V (3Ph + N)

      Precision

      Stationary: ±1%    

      Transitory: ±2% (load variations 100-0-100%)

      Frequency

      50/60 Hz synchronised ±4 %

      With mains absent ±0.05%

      Max. Synchronisation Speed

      ±10 Hz/s

      Waveform

      Pure Sinewave

      Total Harmonic Distortion (THDv)

      <0.5% (Linear Load)

      <1.5% (Non-linear Load)

      Phase Displacement

      120º ±1% (balanced load)

      120º ±2% (imbalances 50% of the load)

      Dynamic Recovery Time

       10 ms. at 98 % of the static value

      Admissible Overload

      Phase Overload:125% for 10 min., 150% for 60 s 

      Total Over load:112.5% for 10 min., 135% for 60 s

      Admissible Crest Factor

      2.8 : 1

      3.2 :1

      3.0 :1

      Admissible Power Factor

      0.7 inductive to 0.7 capacitive 

      Imbalance Output Voltage
      @ 100% Unbalanced Load 

      <1% 

      Current Limit

      High overload, short-circuit: RMS Voltage Limit

       High Crest-Factor current: Peak Voltage Limit 

       

      Type

      Solid state 

      Voltage 

       3x400V (3Ph + N)

      Frequency

      50/60 Hz 

      Activation Criterion

      Microprocessor control 

      Transfer Time 

       Zero seconds

      Admissible Overload

       400% for 10 sec.

      Transfer to Bypass

      Immediate, for overloads above 150%

      Retransfer

      Automatic after alarm clear

      MAINTENANCE BYPASS

      Type

      Without interruption

      Voltage

      3 x 400V (3Ph + N)

      Frequency 

      50/60 Hz 

      Overall Efficiency (Line mode)

       94,00%

      93,00%

      93,30%

      92,80%

      92,60%

      PHYSICAL

      Dimensions, D x W x H(mm)

      805 x 590 x 1320

      850 x 900 x 1500

      Net Weight (without batteries) (Kg)

      215

      255

      550

      Built-in Battery Type (2x31)

       -

      Back-up Time (minutes)

      -

      Net Weight (w/built-in batteries) (Kg)

      -

      -

      -

      MANAGEMENT

      Smart RS-232 / USB

      Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7, Linux, Unix, and MAC

      Optional SNMP

      Power management from SNMP manager and web browser

      NEXT PARTNUMBERS

      LYNX UPS

       77145

       77146

       77147

       77148

        77149

      LYNX Battery extension

      BTO

      BTO

       BTO

       BTO

        BTO

      SNMP/WEB Interface

       included

       included

       included

       included

        included